GF68220

Facility Power Line FiltersGF68220 Mid Performance Series Capacitive Input

GF68220 Mid Performance Series

Capacitive Input 60dB at 14 kHz  (90 dB @ 100 kHz ~ 18 GHz)

EMI/RFI Facility Power Line Filters are used to block unwanted signals and remove interference from entering or exiting through the power lines. Our Mid Performance Filters are specified to 60 dB @ 14 kHz (90 dB @ 100 kHz ~18 GHz).

The GF68220 Facility Power Line Filter is a standalone filter that can be used to replace existing filters in our panel configuration (GFP68221), or if a RF shielded bulkhead is required for your installation.

Download Product Data Sheet:  GF68220 Data Sheet

 

SPECIAL FEATURES
  • Low Pass filter circuits ~ passive components which includes inductors, capacitors, resistors and optional transient suppression devices
  • Manufactured and tested per applicable portions of MIL-PRF-15733
  • Filter cases 16 gage, CRS, plated or painted finish
  • Sealed with welded and soldered seams for shielding effectiveness
  • Discharge resistors incorporated to eliminate potential shock hazard
FUNCTIONAL CHARACTERISTICS
  • Voltage Ratings:
    • 24-1,000 VDC
    • 120/208 VAC (50/60 Hz)
    • 277/480 VAC (50/60 Hz)
  • Voltage Drop:
    • 2% maximum at full rated unity power factor load.
  • Harmonic Distortion:
    • 4% maximum at full rated unity power factor load
  • Temperature Rating:
    • MIL-PRF-15733
  • Current Overload:
    • 140% maximum current rating
  • RF Radiation:
    • Greater than 100 dB isolation
  • Dielectric With-Standing Voltage:
    • 2,200 VDC (prior to installation of discharge resistors)
  • Insulation Resistance:
    • MIL-PRF-15733 (prior to installation of discharge resistors)
  • Insertion loss:
    • 60 dB @ 14 KHz 
    • 90 dB @ 100 KHz to 18 GHz
    • 50/50 Ohm System
APPLICABLE SPECIFICATIONS
  • Military Specifications
    • MIL-PRF-15733 General
  • Military Test Methods
    • MIL-STD-202 Component Parts
    • MIL-STD-220 Insertion Loss
    • MIL-STD-285 Shielding Effectiveness
  • NFPA 70/2011 National Electrical Code Standards
AVAILABLE OPTIONS
  • EMP and Surge Suppressors
  • 400 Hz Filters (lower insertion loss performance)