EMI/RFI facility filters specified to 100 dB are used in government and commercial installations to prevent unwanted signals and interference on power lines. |
Product Summary |
|
Filters · Enclosed terminations · Multi-circuit · 100 dB or 60 dB series Insertion Loss per MIL-STD-220A over the frequency range of 14 kHz to 10 GHz with extended range buffer network · Manufactured and tested per the applicable portions of MIL-F-15733 · Hermetically sealed with welded and soldered seams for shielding effectiveness · Bleeder resistors incorporated to eliminate potential shock hazard · Inductive input for EMP and Surge Protection Enclosure · Modified NEMA type constructed of not less than 14 gauge cold rolled steel · RF tight inner area secured with RF gasket for 100 dB minimum shielding effectiveness, 14 kHz to 10 GHz, minimum · Pre-wired standoffs and lugs · Lifting ears included on heavier enclosures · Front cover access to filters and standoffs |
|
Construction Detail– Facility Panel |

Facility Power Line Filters–Inductive Input |
|
Last Updated: 1007281430 |
Special Features |
Functional Characteristics |
|
· Voltage Rating: · Voltage Drop: · Harmonic Distortion: · Temperature Rating: · Current Overload: · RF Radiation: · Dielectric With-Standing Voltage: · Insulation Resistance: |
|
· MIL-F-15733 · MIL-STD-202 · MIL-STD-220 · MIL-STD-285 · NFPA 70/1987 |
Applicable Specifications |
Available Options |
|
· EMP and surge Suppressors · HUB and Fitting Installation · Legs (12.0 Inch Standard) · Power Factor Correction Coils for 400 Hz |