Text Box: Product Detail

EMI/RFI facility filters specified to 100 dB are used in government and commercial installations to prevent unwanted signals and interference on power lines.

Product Summary

Filters

· Enclosed terminations

· Multi-circuit

· 100 dB or 60 dB series Insertion Loss per MIL-STD-220A over the frequency range of 14 kHz to 10 GHz with extended range buffer network

· Manufactured and tested per the applicable portions of MIL-F-15733

· Hermetically sealed with welded and soldered seams for shielding effectiveness

· Bleeder resistors incorporated to eliminate potential shock hazard

Enclosure

· Modified NEMA type constructed of not less than 14 gauge cold rolled steel

· RF tight inner area secured with RF gasket for 100 dB minimum shielding effectiveness, 14 kHz to 10 GHz, minimum

· Pre-wired standoffs and lugs

· Lifting ears included on heavier enclosures

· Front cover access to filters and standoffs

Construction Detail– Facility Panel

Text Box: Return To Product List
Facility Power Line Filters–
Capacitive Input

Last Updated: 1002241200

Special Features
Functional Characteristics

· Voltage Rating:
120/208 Vac, (50/60, 400 Hz)277/480 Vac, (50/60 Hz)

· Voltage Drop:
2% maximum at full rated unity power factor load.

· Harmonic Distortion:
4% maximum at full rated unity power factor load

· Temperature Rating:
MIL-F-15733 and UL1283

· Current Overload:
140% maximum current rating

· RF Radiation:
Greater than 100 dB isolation

· Dielectric With-Standing Voltage:
2200 Vdc

· Insulation Resistance:
MIL-F-15733 (w/o discharge ckts)

· MIL-F-15733
General specifications for filters, military

· MIL-STD-202
Test methods for components parts, military

· MIL-STD-220
Test methods for insertion loss, military

· MIL-STD-285
Test method for shielding effectiveness

· NFPA 70/1987
National Electrical Code, standards

Applicable Specifications
Available Options

· EMP and surge Suppressors

· HUB and Fitting Installation

· Legs (12.0 Inch Standard)

· Power Factor Correction Coils for 400 Hz

GFP58201   100dB Series
GFP58221     60dB Series

Copyright ©2010 Genisco Filter Corp.           5466 Complex St, Ste 207, San Diego, CA 92123       Phone: (858) 565-7405

Genisco Filter Corp