Facility Filters - Inductive Input
GFP58216 100dB Series
GFP58231 60dB Series

 
       


FILTERS

 

Enclosed terminations

Multi-circuit

100 dB or 60 dB series Insertion Loss per MIL-STD-220A over the frequency range of 14KHz to 10GHz with extended range buffer network

Manufactured and tested per the applicable portions of MIL-F-15733

Hermetically sealed with welded and soldered seams for shielding effectiveness

Bleeder resistors incorporated to eliminate potential shock hazard

Inductive input for EMP and Surge Protection

Harmonic Distortion:
4% maximum at full rated unity power factor load

Temperature Rating:
MIL-F-15733

Current Overload:
140% maximum current rating

RF Radiation:
Greater than 100 dB isolation

Dieletric With-Standing Voltage:
2200 VDC

Insulation Resistance:
MIL-F-15733 (w/o discharge ckts)

APPLICABLE SPECIFICATIONS

MIL-F-15733
General specifications for filters, military

MIL-STD-202
Test methods for components parts, military

MIL-STD-220
Test methods for insertion loss, military

MIL-STD-285
Test method for shielding effectiveness

NFPA 70/1987
National Electrical Code, standards

AVAILABLE OPTIONS

EMP and surge Suppressors

HUB and Fitting Installation

Legs (12.0 Inch Standard)

Power Factor Correction Coils for 400 Hz

 

 

 

ENCLOSURES/PANELS

Modified NEMA type constructed of not less than 14 gauge cold rolled steel

RF tight inner area secured with RF gasket for 100 dB minimum shielding effectiveness, 14 KHz to 10 GHz

Prewired standoffs and lugs

Lifting ears included on heavier enclosures

Front cover access to filters and standoffs

 

 

FUNCTIONAL CHARACTERISTICS

Voltage Rating:
120/208 VAC, (50/60, 400 Hz)277/480 VAC, (50/60 Hz)

Voltage Drop:
2% maximum at full rated unity power factor load.